AHT | constant power heating cable (Ex) up to +425°C

AHT is a unique patented, high power, high temperature, high mechanical strength constant wattage heating cable used for freeze protection and temperature maintenance of pipework and vessels. It has a maximum temperature of 425°C makes it the highest temperature rated cut-to-length heating cable in the world!

General details

AHT is a parallel circuit, mineral insulated, cut-to-length, constant power heating cable of 15 W/m, 30 W/m, 50 W/m, 70 W/m, 100 W/m and 150 W/m output. It is designed for frost protection and heating process of industrial pipes with high temperature. Suitable for use in both, safe and hazardous (Ex) areas, can withstand the temperature of up to +425°C (when switched off).
AHT is a flexible and mechanically robust cable with an extruded aluminium overjacket which, retains some fl exibility and is resistant to high temperature. Available in 100-150 m reel. It is cut-to-length and can be easily connected to a power cable with junction boxes or connectors.

Technical details

Voltage
220/240V AC
Output
15 W/m, 30 W/m, 50 W/m, 70 W/m, 100 W/m and 150 W/m (at +10 °C)
Dimensions
10,7×7,7 mm
Overjacket
Aluminium
Min. bending radius
25 mm
Max. exposure temperature
425°C
Min. operating temperature
-65°C
Min. instal. temperature
–40 °C (CENELEC –20 °C)
Temperature class
See temperature table
Warranty
2 year

Maximum pipe operating temperature (°C)

Type (Ex) zone
T6 T5 T4 T3 T2 T1 Safe
10AHT 34 50 100 188 290 340 340
15AHT - 36 71 160 289 350 350
30AHT - 11 28 100 246 323 323
50AHT - - - 39 178 276 276
70AHT - - - - 48 140 140
100AHT - - - - 48 140 140
150AHT - - - - - 36 36

Maximum circuit length

Type 230V/277V
15AHT 118m
30AHT 83m
50AHT 64m
70AHT 54m
100AHT 46m
150AHT 37m

Application

Type Order No.
10AHT -
15AHT 30123008
30AHT 30123009
50AHT 30123010
70AHT 30123011
100AHT 30123013
150AHT 30123014

Downloads

INSTALLATION AND MAINTENANCE MANUAL

INSTALLATION AND MAINTENANCE MANUAL

AHT PRODUCT DATA SHEET

AHT PRODUCT DATA SHEET

AHT NODE LOCATION

AHT NODE LOCATION

T CLASS LABEL INSTRUCTIONS

T CLASS LABEL INSTRUCTIONS

EC DECLARATION OF CONFORMITY

EC DECLARATION OF CONFORMITY

AHT ATEX CERTIFICATE

AHT ATEX CERTIFICATE

AHT DNV GL CERTIFICATE

AHT DNV GL CERTIFICATE

TECH. DATA SPECIFICATION FOR TANK HEATING

TECH. DATA SPECIFICATION FOR TANK HEATING

TECH. DATA SPECIFICATION FOR PIPE TRACING

TECH. DATA SPECIFICATION FOR PIPE TRACING