FSU-NF | self-limiting heating cable (Ex) up to +250°C

FSU-NF is an industrial grade self-regulating heating cable that can be used for freeze protection or temperature maintenance of pipework and vessels. It can be cut-to-length at the site to match exact piping lengths without any complicated design considerations.

General details

FSU-NF is a self-limiting heating cable of 15 W/m, 30 W/m, 45 W/m, 60 W/m and 75 W/m output for heating and frost protection high-temperature industrial pipes. It can be installed in both safe and hazardous (Ex) areas. The cable produced with nanotechnologies to ensure long-lasting benefits withstands the temperature of up to 250 °c (when switched On or OFF).
FSU-NF cable is made of a fluoropolymer over jacket resistant to the chemically hazardous environment (that of bitumen, oil products, food and industrial oils and other chemical products production).

Installation: for frost protection and temperature maintenance of industrial pipes, oil terminals and refinery, and food industry pipes.

Technical details

Voltage
220/240V AC
Output
15 W/m, 30 W/m, 45 W/m, 60 W/m and 75 W/m (at +10 °C)
Dimensions
12,1×5,4 mm
Overjacket
Fluoropolymer (NF)
Min. bending radius
35 mm
Max temperature when cable switched on
+250 °C
Min operating temperature
-65 °C
Min. instal. temperature
–40 °C (CENELEC –20 °C)
Temperature class
T4
Warranty
2 year

Maximum length of the cable (m) in one electrical circuit depending upon the temperature

Start-up temp. 15FSU
230V
10A 16A 20A 32A 50A
+10°C 76 122 152 172 172
0°C 70 112 140 172 172
-20°C 62 98 172 172 172
-40°C 52 82 102 164 172
Start-up temp. 30FSU
230V
10A 16A 20A 32A 50A
+10°C 52 82 102 172 122
0°C 46 74 92 122 122
-20°C 40 66 82 122 122
-40°C 34 54 68 110 122
Start-up temp. 45FSU
230V
10A 16A 20A 32A 50A
+10°C 38 62 76 100 100
0°C 34 56 70 100 100
-20°C 30 50 62 98 100
-40°C 22 34 44 70 100
Start-up temp. 60SFU
230V
10A 16A 20A 32A 50A
+10°C 30 50 62 86 86
0°C 28 44 56 86 86
-20°C 20 32 40 62 86
-40°C 12 18 24 38 60
Start-up temp. 75FSU
230V
10A 16A 20A 32A 50A
+10°C 22 34 44 70 76
0°C 16 26 34 54 76
-20°C 12 18 24 38 60
-40°C 8 12 14 22 36

Application

Type Order No.
15FSU-NF 30115019
30FSU-NF 30115020
45FSU-NF 30115021
60FSU-NF 30115022
75FSU-NF 30115023

Downloads

INSTALLATION AND MAINTENANCE MANUAL

INSTALLATION AND MAINTENANCE MANUAL

FSU PRODUCT DATA SHEET

FSU PRODUCT DATA SHEET

EC DECLARATION OF CONFORMITY

EC DECLARATION OF CONFORMITY

FSU ATEX CERTIFICATE

FSU ATEX CERTIFICATE

FSU DNV GL CERTIFICATE

FSU DNV GL CERTIFICATE

TECH. SPECIFICATION FOR PIPE TRACING

TECH. SPECIFICATION FOR PIPE TRACING

TECH. SPECIFICATION FOR TANK HEATING

TECH. SPECIFICATION FOR TANK HEATING